Mains Supply -
Mains voltage (L1, L2, L3) -
CSX-xxx-V4 3 x 200 VAC ~ 440 VAC (+ 10% / - 15%)
CSX-xxx-V6 3 x 200 VAC ~ 575 VAC (+ 10% / - 15%)
Mains frequency (at start) 45 Hz to 66 Hz
Rated insulation voltage 600 VAC
Form designation Bypassed semiconductor motor starter form 1
Control Voltage (A1, A2, A3) -
CSX-xxx-xx-C1 110-240 VAC (+ 10% / - 15%)
- or 380-440 VAC (+ 10% / - 15%)
CSX-xxx-xx-C2 24 VAC/VDC (± 20%)
Current consumption (during run) < 100 mA
Current consumption (at power-up) -
CSX-xxx-xx-C1 10 A
CSX-xxx-xx-C2 2 A
Inputs -
Start (terminal 01) Normally Open, 300 VAC max
Stop (terminal 02) Normally Closed, 300 VAC max
Outputs -
Main contactor (terminals 13, 14) Normally Open
- 6 A, 30 VDC resistive / 2 A, 400 VAC, AC11
Environmental -
Degree of protection CSX-007 to CSX-055 IP20
Degree of protection CSX-075 to CSX-110 IP00
Operating temperatures - 10 °C to + 60 °C
Humidity 5% to 95% Relative Humidity
Pollution degree Pollution Degree 3
Vibration IEC 60068 Test Fc Sinusoidal
- 4 Hz to 13.2 Hz: ± 1 mm displacement
- 13.2 Hz to 200 Hz: ± 0.7 g
EMC Emission -
Equipment class (EMC) Class A
Conducted radio frequency emission 0.15 MHz to 0.5 MHz: < 90 dB (µV)
- 0.5 MHz to 5 MHz: < 76 dB (µV)
- 5 MHz to 30 MHz: 80-60 dB (µV)
Radiated radio frequency emission 30 MHz to 230 MHz: < 30 dB (µV/m)
- 230 MHz to 1000 MHz: < 37 dB (µV/m)
- -
This product has been designed as Class A equipment. Use of this product in domestic environments may cause radio interference, in which case the user may be required to employ additional mitigation methods.
EMC Immunity -
Electrostatic discharge 4 kV contact discharge, 8 kV air discharge
Radio frequency electromagnetic field 0.15 MHz to 1000 MHz: 140 dB (µV)
Rated impulse withstand voltage (Fast transients 5/50 ns) 2 kV line to earth, 1 kV line to line
Voltage dip and short time interruption 100 ms (at 40% nominal voltage)
Harmonics and distortion IEC61000-2-4 (Class 3), EN/IEC61800-3
Short Circuit -
Rated short-circuit current CSX-007 to CSX-037 5 kA
Rated short-circuit current CSX-045 to CSX-110 10 kA
Heat Dissipation -
During Start 3 watts / ampere
During Run 10 watts typical
Approvals -
IEC 60947‑4‑2
UL / C-UL UL 508
CE IEC 60947‑4‑2
CCC GB 14048.6
Lloyds IEC 60947‑4‑2