Home arrow IMS2 Specifications

IMS2 Soft Starter: Specifications

Supply -
Mains Voltage -
IMS2xxxx-V5
3 x 200 VAC ~ 525 VAC (3 wire connection)
-
3 x 200 VAC ~ 440 VAC (6 wire connection)
IMS2xxxx-V7
3 x 200 VAC ~ 690 VAC (3 wire connection)
-
3 x 200 VAC ~ 440 VAC (6 wire connection)
Control Voltage -
    IMS2xxxx-xx-C12

110 VAC or 230 VAC (+10%/-15%)

    IMS2xxxx-xx-C24

230 VAC or 400 VAC (+10%/-15%)

    IMS2xxxx-xx-C45

460 VAC or 575 VAC (+10%/-15%)

Mains frequency -
    at start

50 Hz (+/- 2 Hz) or 60 Hz (+/- 2 Hz)

    during start

> 45 Hz (50 Hz supply) or > 55 Hz (60 Hz supply)

    during run

> 48 Hz (50 Hz supply) or > 58 Hz (60 Hz supply)

Control Inputs -
Start (Terminals C23, C24)

Active 24 VDC, 8 mA approx

Stop (Terminals C31, C32)

Active 24 VDC, 8 mA approx

Reset (Terminals C41, C42)

Active 24 VDC, 8 mA approx

Programmable Input A (Terminals C53, C54)

Active 24 VDC, 8 mA approx

Outputs -
Relay Outputs

5 A @ 30 VDC or 250 VAC resistive

-

360 VA inductive

Run Output (Terminals 23, 24)

Normally Open

Programmable Relay Output A (Terminals 13, 14)

Normally Open

Programmable Relay Output B (Terminals 33, 34)
Normally Open
Programmable Relay Output C (Terminals 41, 42, 44)
Changeover
Analogue Output (Terminals B10, B11)
4-20 mA (maximum burden 500 W)
Sundry -
Enclosure rating
-
    IMS2xxxx-xx-xxx-xx-E0

IP00 (open chassis)

    IMS2xxxx-xx-xxx-xx-E4

IP42

    IMS2xxxx-xx-xxx-xx-E5

IP54

Rated short circuit current IMS20018 ~ IMS20897

42 kA

Rated insulation voltage

690 V

Surges

2 kV line to earth, 1 kV line to line

Fast transients

2 kV / 5 kHz

Form designation

Form 1

Electrostatic discharge
4 kV contact discharge, 8 kV air discharge
Equipment class (EMC)

Class A

Radio-frequency electromagnetic field

0.15 MHz – 80 MHz: 140 dBµV

-

80 MHz – 1 GHz: 10 V/m

Pollution degree

Pollution Degree 3

Operating temperatures

- 5 °C ~ + 60 °C

Relative humidity

5% ~ 95% (max non-condensing)

Standards Approvals -
CE
IEC 60947-4-2
UL and C-UL
UL 508
C-tick
IEC 60947-4-2