Supply
|
-
|
|
Mains Voltage
|
-
|
|
MVSxxxx-V02
|
3 x 2300 VAC (± 10%)
|
|
MVSxxxx-V03
|
3 x 3300 VAC (± 10%)
|
|
MVSxxxx-V04
|
3 x 4160 VAC (± 10%)
|
|
MVSxxxx-V06
|
3 x 6600 VAC (± 10%)
|
|
MVSxxxx-V07
|
3 x 7200 VAC (± 10%)
|
|
|
3 x 11000 VAC (± 10%)
|
|
Control Voltage
|
-
|
|
MVSxxxx-xxx-C12
|
110 VAC to 130 VAC (+ 10% / - 15%)
|
|
-
|
or 220 VAC to 240 VAC (+ 10% / - 15%)
|
|
All models
|
500 VA, single phase
|
|
Mains Frequency
|
45 Hz to 66 Hz
|
|
Rated Insulation Voltage
|
-
|
|
MVSxxxx-V02
|
11450 VAC
|
|
MVSxxxx-V03
|
11450 VAC
|
|
MVSxxxx-V04
|
11450 VAC
|
|
MVSxxxx-V06
|
16800 VAC
|
|
MVSxxxx-V07
|
18200 VAC
|
|
MVSxxxx-V11
|
TBA
|
|
Rated Impulse Withstand Voltage (BIL) - Overvoltage Category III
|
-
|
|
MVSxxxx-V02 ~ MVSxxxx-V07
|
45 kV
|
|
MVSxxxx-V11
|
TBA
|
|
Form Designation
|
Bypassed semiconductor motor starter form 1
|
|
Control Inputs
|
-
|
|
Start (Terminals C23, C24)
|
24 VDC, 8 mA approx
|
|
Stop (Terminals C31, C32)
|
24 VDC, 8 mA approx
|
|
Reset (Terminals C41, C42)
|
24 VDC, 8 mA approx
|
|
Input A (Terminals C53, C54)
|
24 VDC, 8 mA approx
|
|
Input B (Terminals C63, C64)
|
24 VDC, 8 mA approx
|
|
Motor Thermistor (Terminals B4, B5)
|
-
|
|
Outputs
|
-
|
|
Relay Outputs
|
10 A @ 250 VAC/ 360 VA
|
|
-
|
10 A @ 30 VDC resistive
|
|
Main Contactor (Terminals 13, 14)
|
Normally Open
|
|
Bypass Contactor (Terminals 23, 24)
|
Normally Open
|
|
Run Output/ PFC (Terminals 33, 34)
|
Normally Open
|
|
Output Relay A (Terminals 43, 44)
|
Normally Open
|
|
Output Relay B (Terminals 51, 52, 54)
|
Changeover
|
|
Output Relay C (Terminals 61, 62, 64)
|
Changeover
|
|
Analog Output (Terminals B10, B11)
|
0-20 mA or 4-20 mA
|
|
Environmental
|
-
|
|
Degree of Protection
|
-
|
|
Power Assembly
|
IP00
|
|
Controller
|
IP54/ NEMA 12
|
|
Operating Temperature
|
- 10 ˚C to + 60 ˚C
|
|
Storage Temperature
|
- 25 ˚C to + 55 ˚C
|
|
-
|
- 25 ˚C to + 70 ˚C (< 24 hours)
|
|
Humidity
|
5% to 95% Relative Humidity
|
|
Pollution Degree
|
Pollution Degree 3
|
|
Vibration
|
Designed to IEC 60068 Test Fc Sinusoidal
|
|
-
|
4 Hz to 13.2 Hz: ± 1 mm displacement
|
|
-
|
13.2 Hz to 200 Hz: ± 0.7 g
|
|
EMC Emission
|
-
|
|
Equipment Class (EMC)
|
Class A
|
|
Conducted Radio Frequency Emission
|
10 kHz to 150 kHz: < 120 - 69 dB µV
|
|
-
|
0.15 MHz to 0.5 MHz: < 79 dB µV
|
|
-
|
0.5 MHz to 30 MHz: < 73 dB µV
|
|
Radiated Radio Frequency Emission
|
0.15 MHz to 30 MHz: < 80-50 dB µV/m
|
|
-
|
30 MHz to 100 MHz: < 60-54 dB µV/m
|
|
-
|
100 MHz to 2000 MHz: < 54 dB µV/m
|
|
-
|
-
|
|
This product has been designed for Class A equipment. Use of the product in domestic environments may cause radio interference, in which case the user may be required to employ additional mitigation methods.
|
|
EMC Immunity
|
-
|
|
Electrostatic Discharge
|
6 kV contact discharge, 8 kV air discharge
|
|
Radio Frequency Electromagnetic Field
|
80 MHz to 1000 MHz: 10 V/m
|
|
Fast Transients
|
5/50 ns (main and control circuits)
|
|
-
|
2 kV line to earth, 1 kV line to line
|
|
Surges 1.2/50 µs (main and control circuits)
|
2 kV line to earth, 1 kV line to line
|
|
Voltage dip and short time interruption
|
5000 ms (at 0% nominal voltage)
|
|
-
|
(safe shutdown)
|
|
Short Circuit
|
-
|
|
Rated short-circuit current, symmetrical, fused (Class E2)
|
-
|
|
MVSxxxx-V02 ~ MVSxxxx-V07
|
48 kA
|
|
MVSxxxx-V11
|
TBA
|
|
Heat Dissipation (Steady State)
|
-
|
|
Power Assembly (SCRs bypassed)
|
20 W approx
|
|
Controller
|
10 W approx
|
|
Standards Approvals
|
-
|
|
Cü
|
EMC requirements
|
|
UL/ C-UL
|
UL 508, UL 347
|
|
CE
|
EMC EU Directive
|
|
Marine
|
Lloyd's Register
|