Home arrow MVS Specifications

MVS Specifications


Supply

-

Mains Voltage

-

MVSxxxx-V02

3 x 2300 VAC (± 10%)

MVSxxxx-V03

3 x 3300 VAC (± 10%)

MVSxxxx-V04

3 x 4160 VAC (± 10%)

MVSxxxx-V06

3 x 6600 VAC (± 10%)

MVSxxxx-V07

3 x 7200 VAC (± 10%)

MVSxxxx-V11

3 x 11000 VAC (± 10%)

Control Voltage

-

MVSxxxx-xxx-C12

110 VAC to 130 VAC (+ 10% / - 15%)

-

or 220 VAC to 240 VAC (+ 10% / - 15%)

All models

500 VA, single phase

Mains Frequency

45 Hz to 66 Hz

Rated Insulation Voltage

-

MVSxxxx-V02

11450 VAC

MVSxxxx-V03

11450 VAC

MVSxxxx-V04

11450 VAC

MVSxxxx-V06

16800 VAC

MVSxxxx-V07

18200 VAC

MVSxxxx-V11

TBA

Rated Impulse Withstand Voltage (BIL) - Overvoltage Category III

-

MVSxxxx-V02 ~ MVSxxxx-V07

45 kV

MVSxxxx-V11

TBA

Form Designation

Bypassed semiconductor motor starter form 1

Control Inputs

-

Start (Terminals C23, C24)

24 VDC, 8 mA approx

Stop (Terminals C31, C32)

24 VDC, 8 mA approx

Reset (Terminals C41, C42)

24 VDC, 8 mA approx

Input A (Terminals C53, C54)

24 VDC, 8 mA approx

Input B (Terminals C63, C64)

24 VDC, 8 mA approx

Motor Thermistor (Terminals B4, B5)

-

Outputs

-

Relay Outputs

10 A @ 250 VAC/ 360 VA

-

10 A @ 30 VDC resistive

Main Contactor (Terminals 13, 14)

Normally Open

Bypass Contactor (Terminals 23, 24)

Normally Open

Run Output/ PFC (Terminals 33, 34)

Normally Open

Output Relay A (Terminals 43, 44)

Normally Open

Output Relay B (Terminals 51, 52, 54)

Changeover

Output Relay C (Terminals 61, 62, 64)

Changeover

Analog Output (Terminals B10, B11)

0-20 mA or 4-20 mA

Environmental

-

Degree of Protection

-

Power Assembly

IP00

Controller

IP54/ NEMA 12

Operating Temperature

- 10 ˚C to + 60 ˚C

Storage Temperature

- 25 ˚C to + 55 ˚C

-

- 25 ˚C to + 70 ˚C (< 24 hours)

Humidity

5% to 95% Relative Humidity

Pollution Degree

Pollution Degree 3

Vibration

Designed to IEC 60068 Test Fc Sinusoidal

-

4 Hz to 13.2 Hz: ± 1 mm displacement

-

13.2 Hz to 200 Hz: ± 0.7 g

EMC Emission

-

Equipment Class (EMC)

Class A

Conducted Radio Frequency Emission

10 kHz to 150 kHz: < 120 - 69 dB µV

-

0.15 MHz to 0.5 MHz: < 79 dB µV

-

0.5 MHz to 30 MHz: < 73 dB µV

Radiated Radio Frequency Emission

0.15 MHz to 30 MHz: < 80-50 dB µV/m

-

30 MHz to 100 MHz: < 60-54 dB µV/m

-

100 MHz to 2000 MHz: < 54 dB µV/m

-

-

This product has been designed for Class A equipment. Use of the product in domestic environments may cause radio interference, in which case the user may be required to employ additional mitigation methods.

EMC Immunity

-

Electrostatic Discharge

6 kV contact discharge, 8 kV air discharge

Radio Frequency Electromagnetic Field

80 MHz to 1000 MHz: 10 V/m

Fast Transients

5/50 ns (main and control circuits)

-

2 kV line to earth, 1 kV line to line

Surges 1.2/50 µs (main and control circuits)

2 kV line to earth, 1 kV line to line

Voltage dip and short time interruption

5000 ms (at 0% nominal voltage)

-

(safe shutdown)

Short Circuit

-

Rated short-circuit current, symmetrical, fused (Class E2)

-

MVSxxxx-V02 ~ MVSxxxx-V07

48 kA

MVSxxxx-V11

TBA

Heat Dissipation (Steady State)

-

Power Assembly (SCRs bypassed)

20 W approx

Controller

10 W approx

Standards Approvals

-

EMC requirements

UL/ C-UL

UL 508, UL 347

CE

EMC EU Directive

Marine

Lloyd's Register