| Mains voltage (L1, L2, L3) |
|
| CSXi-xxx-V4 |
3 x 200 VAC ~ 440 VAC (+ 10% / - 15%) |
| CSXi-xxx-V6 |
3 x 200 VAC ~ 575 VAC (+ 10% / - 15%) |
| Mains frequency (at start) |
45 Hz to 66 Hz |
| Rated insulation voltage |
600 VAC |
| Control Voltage (A1, A2, A3) |
|
| CSXi-xxx-xx-C1 |
110-240 VAC (+ 10% / - 15%) |
| |
or 380-440 VAC (+ 10% / - 15%) |
| CSXi-xxx-xx-C2 |
24 VAC/VDC (± 20%) |
| Current consumption (during run) |
< 100 mA |
| Current consumption (at power-up) |
|
| CSXi-xxx-xx-C1 |
10A |
| CSXi-xxx-xx-C2 |
2 A |
| Start (terminal 01) |
Normally Open, 300 VAC max |
| Stop (terminal 02) |
Normally Closed, 300 VAC max |
| Main contactor (terminals 13, 14) |
Normally Open |
| |
6 A, 30 VDC resistive / 2 A, 400 VAC, AC11 |
| Programmable relay (terminals 23, 24) |
Normally Open |
| |
6 A, 30 VDC resistive / 2 A, 400 VAC, AC11 |
| Degree of protection CSXi-007 to CSXi-055 |
IP20 |
| Degree of protection CSXi-075 to CSXi-110 |
IP00 |
| Operating temperatures |
- 10 °C to + 60 °C |
| Humidity |
5% to 95% Relative Humidity |
| Pollution degree |
Pollution Degree 3 |
| Vibration |
IEC 60068 Test Fc Sinusoidal |
| |
4 Hz to 13.2 Hz: ± 1 mm displacement |
| |
13.2 Hz to 200 Hz: ± 0.7 g |
| Equipment class (EMC) |
Class A |
| Conducted radio frequency emission |
0.15 MHz to 0.5 MHz: < 90 dB (µV) |
| |
0.5 MHz to 5 MHz: < 76 dB (µV) |
| |
5 MHz to 30 MHz: 80-60 dB (µV) |
| Radiated radio frequency emission |
30 MHz to 230 MHz: < 30 dB (µV/m) |
| |
230 MHz to 1000 MHz: < 37 dB (µV/m) |
| This product has been designed as Class A equipment. Use of this product in domestic environments may cause radio interference, in which case the user may be required to employ additional mitigation methods. |
| Electrostatic discharge |
4 kV contact discharge, 8 kV air discharge |
| Radio frequency electromagnetic field |
0.15 MHz to 0.5 MHz: < 90 dB (µV) |
| Rated impulse withstand voltage (Fast transients 5/50 ns) |
2 kV line to earth, 1 kV line to line |
| Voltage dip and short time interruption |
100 ms (at 40% nominal voltage) |
| Harmonics and distortion |
IEC61000-2-4 (Class 3), EN/IEC61800-3 |
| Rated short-circuit current CSXi-007 to CSXi-037 |
5 kA |
| Rated short-circuit current CSXi-045 to CSX-i110 |
10 kA |
| Heat Dissipation |
|
| During Start |
3 watts / ampere |
| During Run |
10 watts typical |
| C |
IEC 60947 4 2 |
| UL / C-UL |
UL 508 |
| CE |
IEC 60947 4 2 |
| CCC |
GB 14048.6 |
| Lloyds |
IEC 60947 4 2 |