IMS2 Soft Starter: Specifications

Supply  
Mains Voltage  
IMS2xxxx-V5
3 x 200 VAC ~ 525 VAC (3 wire connection)

3 x 200 VAC ~ 440 VAC (6 wire connection)
IMS2xxxx-V7
3 x 200 VAC ~ 690 VAC (3 wire connection)

3 x 200 VAC ~ 440 VAC (6 wire connection)
Control Voltage  
    IMS2xxxx-xx-C12 110 VAC or 230 VAC (+10%/-15%)
    IMS2xxxx-xx-C24 230 VAC or 400 VAC (+10%/-15%)
    IMS2xxxx-xx-C45 460 VAC or 575 VAC (+10%/-15%)
Mains frequency  
    at start 50 Hz (+/- 2 Hz) or 60 Hz (+/- 2 Hz)
    during start > 45 Hz (50 Hz supply) or > 55 Hz (60 Hz supply)
    during run > 48 Hz (50 Hz supply) or > 58 Hz (60 Hz supply)
Control Inputs  
Start (Terminals C23, C24) Active 24 VDC, 8 mA approx
Stop (Terminals C31, C32) Active 24 VDC, 8 mA approx
Reset (Terminals C41, C42) Active 24 VDC, 8 mA approx
Programmable Input A (Terminals C53, C54) Active 24 VDC, 8 mA approx
Outputs  
Relay Outputs 5 A @ 30 VDC or 250 VAC resistive
  360 VA inductive
Run Output (Terminals 23, 24) Normally Open
Programmable Relay Output A (Terminals 13, 14) Normally Open
Programmable Relay Output B (Terminals 33, 34)
Normally Open
Programmable Relay Output C (Terminals 41, 42, 44)
Changeover
Analogue Output (Terminals B10, B11)
4-20 mA (maximum burden 500 W)
Sundry  
Enclosure rating

    IMS2xxxx-xx-xxx-xx-E0 IP00 (open chassis)
    IMS2xxxx-xx-xxx-xx-E4 IP42
    IMS2xxxx-xx-xxx-xx-E5 IP54
Rated short circuit current IMS20018 ~ IMS20897 42 kA
Rated insulation voltage 690 V
Surges 2 kV line to earth, 1 kV line to line
Fast transients 2 kV / 5 kHz
Form designation Form 1
Electrostatic discharge
4 kV contact discharge, 8 kV air discharge
Equipment class (EMC) Class A
Radio-frequency electromagnetic field 0.15 MHz – 80 MHz: 140 dBµV
  80 MHz – 1 GHz: 10 V/m
Pollution degree Pollution Degree 3
Operating temperatures - 5 °C ~ + 60 °C
Relative humidity 5% ~ 95% (max non-condensing)
Standards Approvals  
CE
IEC 60947-4-2
UL and C-UL
UL 508
C-tick
IEC 60947-4-2