Home arrow Tech Topics arrow Motor Circuit Configurations arrow Type 2 Circuit Protection: How do I achieve Type 2 protection of a soft starter?

Type 2 Circuit Protection: How do I achieve Type 2 protection of a soft starter? 

Type 2 protection requires that in the event of a short circuit on the output of a soft starter the fault must be cleared without risk of injury to personnel or damage to the soft starter.

Type 2 protection is achieved by using semiconductor fuses. These fuses must be able to carry motor start current and have a total clearing I2t < the I2t of the soft starter SCRs.

Semiconductor fuses for Type 2 circuit protection are additional to HRC fuses or MCCBs that form part of the motor branch circuit protection.



Refer to the soft starter's Product Guide for semiconductor fuse recommendations.