Type 2 Circuit Protection: How do I achieve Type 2 protection of a soft starter? |
|
Type 2 protection requires that in the event of a short circuit on the output of a soft starter the fault must be cleared without risk of injury to personnel or damage to the soft starter. Type 2 protection is achieved by using semiconductor fuses. These fuses must be able to carry motor start current and have a total clearing I2t < the I2t of the soft starter SCRs. Semiconductor fuses for Type 2 circuit protection are additional to HRC fuses or MCCBs that form part of the motor branch circuit protection.
Refer to the soft starter's User Manual for semiconductor fuse recommendations. |