MVS: Specifications

    Supply

          
    Mains Voltage    
     MVSxxxx-V02
      3 x 2300 VAC (± 10%)
     MVSxxxx-V03
      3 x 3300 VAC (± 10%)
     MVSxxxx-V04
      3 x 4160 VAC (± 10%)
     MVSxxxx-V06
      3 x 6600 VAC (± 10%)
     MVSxxxx-V07
      3 x 7200 VAC (± 10%)
     MVSxxxx-V13
      3 x 13800 VAC (± 10%)
    Control Voltage    
     MVSxxxx-xxx-C12   110 VAC to 130 VAC (+ 10% / - 15%)
        or 220 VAC to 240 VAC (+ 10% / - 15%)
    All models   500 VA, single phase
    Mains Frequency   45 Hz to 66 Hz
    Rated Power Frequency Withstand Voltage (Ud)
     MVSxxxx-V02 ~ MVSxxxx-V04   11450 VAC
     MVSxxxx-V06 ~ MVSxxxx-V07   20000 VAC
     MVSxxxx-V13   35000 VAC
    Rated Lightning Impulse Withstand Voltage (BIL) - Overvoltage Category III (Up)
     MVSxxxx-V02 ~ MVSxxxx-V07   45 kV
     MVSxxxx-V13   85 kV
    Form Designation   Bypassed semiconductor motor starter form 1


    Control Inputs

       
    Start (Terminals C23, C24)   24 VDC, 8 mA approx
    Stop (Terminals C31, C32)   24 VDC, 8 mA approx
    Reset (Terminals C41, C42)   24 VDC, 8 mA approx
    Input A (Terminals C53, C54)   24 VDC, 8 mA approx
    Input B (Terminals C63, C64)   24 VDC, 8 mA approx
    Motor Thermistor (Terminals B4, B5)    


    Outputs

       
    Relay Outputs   10 A @ 250 VAC/ 360 VA
        10 A @ 30 VDC resistive
    Main Contactor (Terminals 13, 14)   Normally Open
    Bypass Contactor (Terminals 23, 24)   Normally Open
    Run Output/ PFC (Terminals 33, 34)   Normally Open
    Output Relay A (Terminals 43, 44)   Normally Open
    Output Relay B (Terminals 51, 52, 54)   Changeover
    Output Relay C (Terminals 61, 62, 64)   Changeover
    Analog Output (Terminals B10, B11)   0-20 mA or 4-20 mA


    Environmental

       
    Degree of Protection    
    Power Assembly   IP00
    Controller   IP54/ NEMA 12
    Operating Temperature   - 10 °šC to + 55 °šC
    Storage Temperature   - 25 °šC to + 55 °šC
    Humidity   5% to 95% Relative Humidity
    Pollution Degree   Pollution Degree 3
    Vibration   Designed to IEC 60068


    EMC Emission

       
    Equipment Class (EMC)   Class A
    Conducted Radio Frequency Emission   10 kHz to 150 kHz: < 120 - 69 dB µV
        0.15 MHz to 0.5 MHz: < 79 dB µV
        0.5 MHz to 30 MHz: < 73 dB µV
    Radiated Radio Frequency Emission   0.15 MHz to 30 MHz: < 80-50 dB µV/m
        30 MHz to 100 MHz: < 60-54 dB µV/m
        100 MHz to 2000 MHz: < 54 dB µV/m
         
    This product has been designed for Class A equipment. Use of the product in domestic environments may cause radio interference, in which case the user may be required to employ additional mitigation methods.


    EMC Immunity

       
    Electrostatic Discharge   6 kV contact discharge, 8 kV air discharge
    Radio Frequency Electromagnetic Field   80 MHz to 1000 MHz: 10 V/m
    Fast Transients   5/50 ns (main and control circuits)
        2 kV line to earth, 1 kV line to line
    Surges 1.2/50 µs (main and control circuits)   2 kV line to earth, 1 kV line to line
    Voltage dip and short time interruption   5000 ms (at 0% nominal voltage)
        (safe shutdown)


    Short Circuit

       
    Rated short-circuit current, symmetrical, fused (Class E2)    
    MVSxxxx-V02 ~ MVSxxxx-V07   48 kA
    MVSxxxx-V13   75 kA
    Power Assembly (SCRs bypassed)   20 W approx
    Controller   10 W approx


    Standards Approvals

       
    C√   EMC requirements
    CE   EMC EU Directive