CSXi: Specifications

Mains Supply

      
Mains voltage (L1, L2, L3)    
CSXi-xxx-V4   3 x 200 VAC ~ 440 VAC (+ 10% / - 15%)
CSXi-xxx-V6   3 x 200 VAC ~ 575 VAC (+ 10% / - 15%)
Mains frequency (at start)   45 Hz to 66 Hz
Rated insulation voltage   600 VAC
Form designation   Bypassed semiconductor motor starter form 1
Control Voltage (A1, A2, A3)    
CSXi-xxx-xx-C1   110-240 VAC (+ 10% / - 15%)
    or 380-440 VAC (+ 10% / - 15%)
CSXi-xxx-xx-C2   24 VAC/VDC (± 20%)
Current consumption (during run)   < 100 mA
Current consumption (at power-up)    
CSXi-xxx-xx-C1   10 A
CSXi-xxx-xx-C2   2 A


Inputs

   
Start (terminal 01)   Normally Open
    150 kΩ @ 300 VAC and 5.6 kΩ @ 24 VAC/VDC
Stop (terminal 02)   Normally Closed
    150 kΩ @ 300 VAC and 5.6 kΩ @ 24 VAC/VDC


Outputs

   
Main contactor (terminals 13, 14)   Normally Open
    6 A, 30 VDC / 6 A, 250 VAC resistive
Programmable relay (terminals 23, 24)   Normally Open
    6 A, 30 VDC / 6 A, 250 VAC resistive


Environmental

   
Degree of protection CSXi-007 to CSX-055   IP20
Degree of protection CSXi-075 to CSX-110   IP00
Operating temperatures   - 10 °C to + 60 °C
Humidity   5% to 95% Relative Humidity
Pollution degree   Pollution Degree 3
Vibration   IEC 60068 Test Fc Sinusoidal
    4 Hz to 13.2 Hz: ± 1 mm displacement
    13.2 Hz to 200 Hz: ± 0.7 g


EMC Emission

   
Equipment class (EMC)   Class B
Conducted radio frequency emission   0.15 MHz to 0.5 MHz: < 56-46 dB (µV)
    0.5 MHz to 5 MHz: < 46 dB (µV)
    5 MHz to 30 MHz: 50 dB (µV)
Radiated radio frequency emission   30 MHz to 230 MHz: < 30 dB (µV/m)
    230 MHz to 1000 MHz: < 37 dB (µV/m)
     
This product has been designed as Class A equipment. Use of this product in domestic environments may cause radio interference, in which case the user may be required to employ additional mitigation methods.


EMC Immunity

   
Electrostatic discharge   4 kV contact discharge, 8 kV air discharge
Radio frequency electromagnetic field   0.15 MHz to 1000 MHz: 140 dB (µV)
Rated impulse withstand voltage (Fast transients 5/50 ns)   2 kV line to earth, 1 kV line to line
Voltage dip and short time interruption   100 ms (at 40% nominal voltage)
Harmonics and distortion   IEC61000-2-4 (Class 3), EN/IEC61800-3


Short Circuit

   
Rated short-circuit current CSX-007 to CSX-037   5 kA
Rated short-circuit current CSX-045 to CSX-110   10 kA


Heat Dissipation

   
During Start   3 watts / ampere
During Run   10 watts typical


Approvals

   
RCM   IEC 60947-4-2
CE   EN 60947-4-2
CCC   GB 14048.6
EAC   TP TC 004/2011, TP TC 020/2011
Marine   Lloyds Marine No 1 Specification
UL / C-UL   UL 508