General |
||
Current Range | 23 A ~ 1600 A (nominal) | |
Motor connection | In-line or inside delta | |
Bypass | Integrated internal or external | |
|
||
Mains Voltage (L1, L2, L3) | ||
EMX3-xxxx-V4 | 200 VAC ~ 440 VAC (± 10%) | |
EMX3-xxxx-V7 | 380 VAC ~ 690 VAC (± 10%) (in-line connection) | |
EMX3-xxxx-V7 | 380 VAC ~ 600 VAC (± 10%) (inside delta connection) | |
Control Voltage | (A1, A2, A3) 110 ~ 220 VAC (+ 10% / -15%) | |
or 230 ~ 440 VAC (+ 10% / -15%) | ||
Mains Frequency | 45 Hz to 66 Hz | |
|
||
Inputs | Active 24 VDC, 8 mA approx. | |
Start (C23, C24) | Normally open | |
Stop (C31, C32) | Normally closed | |
Reset (C41, C42) | Normally open or closed | |
Programmable Inputs | ||
Input A (C53, C54) | Normally open or closed | |
Input B (C63, C64) | Normally open or closed | |
Motor Thermistor (B4, B5) | ||
PT100 RTD (B6, B7, B8) | ||
|
||
Relay outputs | 10 A at 250 VAC resistive | |
5 A at 250 VAC, AC15 pf 0.3 | ||
Run Relay (23, 24) | Normally Open | |
Programmable Outputs | ||
Relay A (13, 14) | Normally Open | |
Relay B (31, 32, 34) | Changeover | |
Relay C (41, 42, 44) | Changeover | |
Analog Output (B10, B11) | 0-20 mA or 4-20 mA | |
24 VDC Output (P24, COM) | 200 mA | |
|
||
Ingress protection: | ||
EMX3-0023B ~ EMX3-0105B | IP20 | |
EMX3-0145B ~ EMX3-1600C | IP00 | |
Operating temperature | -10 °C ~ 60 °C | |
Storage temperature | - 10 °C ~ 60 °C | |
Humidity | 5% to 95% Relative Humidity |